Superior™ Digital Chlorine Vacuum Alarm Switch, VAS-4

Item No.69700
Product Details Alerts to both high and low vacuum conditions Ensures your chlorination process is operating correctly Many states now require vacuum level monitoring on all public water supply gas chlorination systems This quick, reliable monitoring device alerts you if the chlorinating process has
Price $903
price per each
excl. tax
In Stock

Description

Product Details
  • Alerts to both high and low vacuum conditions
  • Ensures your chlorination process is operating correctly
  • Many states now require vacuum level monitoring on all public water supply gas chlorination systems

This quick, reliable monitoring device alerts you if the chlorinating process has been interrupted when either of two critical situations arise. High Vacuum Alarm indicates that the chlorine gas supply has been interrupted because the chlorine supply is empty or the cylinder valve has been shut off. Low Vacuum Alarm indicates that the ejector is not producing sufficient vacuum to operate the system, or a leak has occurred somewhere in the system.

The vacuum sensor is housed in an oil-based chlorine protection device that connects to your feed system with 1/4" tubing between the ejector and rate valve. A separate NEMA 4X enclosure includes alarm indicator LEDs, an LED display for vacuum level, and controls for adjusting setpoints and time delay. Use output relays with an optional A/V alarm, or connect to other devices like an autodialer or SCADA.

Tech Specs:
  • Alarms:
    High vacuum: adjustable range, preset at 20" Hg
    Low vacuum: adjustable range, preset at 5" Hg
  • Time delay: 0 to 60 seconds, adjustable
  • Relay outputs: NO/NC type, 240 VAC @ 5A, 115 VAC @ 5A, 30 VDC @ 5A
  • Analog outputs: 0-3 VDC, 0-3 ma DC
  • Enclosure: NEMA 4X
  • Power: 120-240 VAC, 50/60Hz, 6'L power cord with 120V plug

Product Information

Item number
69700
Brand Name
Chemical Injection Technologies - Superior
Catalog Page
193
Net weight
3
Condition
New

Documents

Superior™ Digital Chlorine Vacuum Alarm Switch, VAS-4

Item number
69700
Brand Name
Chemical Injection Technologies - Superior
Catalog Page
193
Net weight
3
Condition
New
Price $903
price per each
excl. tax
In Stock
each
Need Help? Call 800-548-1234
Product Details
  • Alerts to both high and low vacuum conditions
  • Ensures your chlorination process is operating correctly
  • Many states now require vacuum level monitoring on all public water supply gas chlorination systems

This quick, reliable monitoring device alerts you if the chlorinating process has been interrupted when either of two critical situations arise. High Vacuum Alarm indicates that the chlorine gas supply has been interrupted because the chlorine supply is empty or the cylinder valve has been shut off. Low Vacuum Alarm indicates that the ejector is not producing sufficient vacuum to operate the system, or a leak has occurred somewhere in the system.

The vacuum sensor is housed in an oil-based chlorine protection device that connects to your feed system with 1/4" tubing between the ejector and rate valve. A separate NEMA 4X enclosure includes alarm indicator LEDs, an LED display for vacuum level, and controls for adjusting setpoints and time delay. Use output relays with an optional A/V alarm, or connect to other devices like an autodialer or SCADA.

Tech Specs:
  • Alarms:
    High vacuum: adjustable range, preset at 20" Hg
    Low vacuum: adjustable range, preset at 5" Hg
  • Time delay: 0 to 60 seconds, adjustable
  • Relay outputs: NO/NC type, 240 VAC @ 5A, 115 VAC @ 5A, 30 VDC @ 5A
  • Analog outputs: 0-3 VDC, 0-3 ma DC
  • Enclosure: NEMA 4X
  • Power: 120-240 VAC, 50/60Hz, 6'L power cord with 120V plug