Time Mark 261 Series Alternating Relay w/o Toggle, 20-28 VAC/VDC, 261XBXPR24
Description
- 261 Series (Struthers Dunn Replacement) Relays: Alternate Two Motors; Begin On Closing Switch
- Solid-state reliability
- Heavy-duty contact ratings
The Model 261 series Alternating Relay is designed for duplex pumping systems where it is desirable to equalize pump run time. The solid-state alternating circuit drives an internal electromechanical relay. A continuous power source and control switch are required.
The control switch (float, pressure or other isolated contact) is connected between the L1 terminal and the control terminal. Each time the control switch is opened the output contacts will change states. Indicator lights on the case show the internal relay status.
The Model 261XBXP(R) Alternating Relay uses the same solid-state latching and control circuit as all the other 261 series models, the enclosure and the connecting base being the major differences.
This version was designed to replace a long time and widely used mechanical latching relay offered by another manufacturer. The modern circuitry used the Model 261XBXP offers a vast improvement in reliability and useful life over the mechanical type. The XBXP version of the relay requires closing the control switch to begin alternation, and the XBXPR version requires opening the control switch to begin alternation.
Replacement of the original mechanical alternator with the Model 261XBXP requires the addition of wire from L1 to Pin 5 of the connector in order to supply continuous power to the solid-state circuit.
- Control voltage (VAC/DC): 20 to 28
- # of pumps/loads: 2
- Mounting: 12-pin
- Contact form: DPDT
- Contact rating: 10 amps
Product Information
- Item number
- 65984
- Brand Name
- Time Mark
- Net weight
- 0.4
- Condition
- New
Time Mark 261 Series Alternating Relay w/o Toggle, 20-28 VAC/VDC, 261XBXPR24
- Item number
- 65984
- Brand Name
- Time Mark
- Net weight
- 0.4
- Condition
- New
- 261 Series (Struthers Dunn Replacement) Relays: Alternate Two Motors; Begin On Closing Switch
- Solid-state reliability
- Heavy-duty contact ratings
The Model 261 series Alternating Relay is designed for duplex pumping systems where it is desirable to equalize pump run time. The solid-state alternating circuit drives an internal electromechanical relay. A continuous power source and control switch are required.
The control switch (float, pressure or other isolated contact) is connected between the L1 terminal and the control terminal. Each time the control switch is opened the output contacts will change states. Indicator lights on the case show the internal relay status.
The Model 261XBXP(R) Alternating Relay uses the same solid-state latching and control circuit as all the other 261 series models, the enclosure and the connecting base being the major differences.
This version was designed to replace a long time and widely used mechanical latching relay offered by another manufacturer. The modern circuitry used the Model 261XBXP offers a vast improvement in reliability and useful life over the mechanical type. The XBXP version of the relay requires closing the control switch to begin alternation, and the XBXPR version requires opening the control switch to begin alternation.
Replacement of the original mechanical alternator with the Model 261XBXP requires the addition of wire from L1 to Pin 5 of the connector in order to supply continuous power to the solid-state circuit.
- Control voltage (VAC/DC): 20 to 28
- # of pumps/loads: 2
- Mounting: 12-pin
- Contact form: DPDT
- Contact rating: 10 amps